Class A Insulated Inorganic Fabric Fire Curtain

Jul 03, 2026

Leave a message

 

 

Fire Linkage Control and Commissioning

 

 

 

Inspection of Electric Control and Fire Linkage System

 

☐ Smoke detectors and heat detectors are connected to two separate independent circuits and shall not share one loop.

 

☐ NH fire-resistant copper cables shall be adopted for linkage wiring, routed through hot-dip galvanized fire-resistant steel conduits.

 

☐ A weatherproof local push-button station with UP/DOWN/STOP functions shall be mounted on the side wall of the opening at a height of 1.4 m.

 

☐ When smoke and heat alarm signals are activated simultaneously, the fire curtain shall fully lower to the ground to fully close the opening.

 

☐ The main control panel in the fire control room is capable of receiving feedback signals including intermediate stop, full descent and equipment failure of the fire curtain.

 

 

34f3e12566a9f0ff64af7582eac95f8b

 

 

Comprehensive On-site Test & Inspection of Commissioning Functions

☐ The fire curtain operates smoothly without jamming throughout the full travel range including lifting, mid-position stop and lowering.

 

☐ Remote control via fire control main panel and local push-button control function properly.

 

☐ Upon power failure, the thermal release device can lower the curtain automatically to form fire separation.

 

☐ No vehicles or pipelines permanently occupy the vertical travel clearance of the fire curtain.

 

☐ Operational warning signs and emergency release operation instructions are posted on site.

9506a5cce611b3cc9888856b8a576dff
 

Inspection of Sealing Clearance & Floor Smoke Barrier

 

 

☐ The side gap between curtain fabric and guide rail shall not exceed 5 mm, with no obvious light-transmitting or smoke leakage passages.

☐ After the fire curtain lands, the bottom rubber strip fits closely to the ground, and the clearance is ≤ 10 mm.

☐ All intumescent rubber strips are free from aging, hardening and falling off, and their fire expansion sealing function remains intact.

☐ No large-area light transmission, air leakage or bulging occurs during the whole lifting and lowering process.

4f9f2cba2ca553faa2f57739b22a92be

 

 

 

 

On-site Acceptance Inspection of Class A Insulated Inorganic Fire Curtain

 

 

Verification of Product Qualifications and Type Test Documents

□ Valid 3C Compulsory Product Certification Certificate available, and the product model matches the on-site

physical product

□ Type test report for Class A (Insulated, E+I) provided, with fire resistance rating complying with design requirements (E180/E120/E90)

□ Complete factory certificates and separate test reports for motors, electric control systems and temperature control devices
□ Class A non-combustible material test reports provided for curtain fabric, tracks, fire sealing strips and rock wool

dc7af76e13f3595bc6140e5f2a4b3679

834M

3C Compulsory Product Certification Certificate

732M

Class A (Insulated, Integrity + Insulation)

90M

Complete factory certificates for fire curtains

236M

Class A non-combustible material

 

 

 

 